Switchgear Procurement | RFP #2023-20 Addendum #3 1000 Col. Eileen Collins Blvd. Syracuse, NY 13212 ADDENDUM #03 p – 315.454.3263 f – 315.454.8757 bids@syrairport.org September 21, 2023 RFI #1: Can you please advise if traditional Non-Arc Resistant Switchgear will be considered based on lead time and cost impact to the project? Response: Arc Resistant Switchgear is required. Ideally, the full switchgear lineup including the switches should be Arc Resistant. If this is not feasible in the manufacturers design, please identify what components/compartments will not be Arc Resistant as a deviation. Proper labeling would be required identifying which components/compartments are not Arc Resistant if the proposal/deviation are accepted. flysyracuse.com